Product / Harmonic distortionExplainer

What an Active Harmonic Filter Fixes, and What It Leaves

An active harmonic filter cleans the current where it connects, which is usually beside the meter. HarmoniQ removes harmonics close to where they start, with the reactive current and imbalance that travel with them.

Topic
Harmonic distortion
Applies to
Commercial and industrial sites
Reading time
5 minutes
Inside
3 exhibits

In brief

  1. Harmonics are currents at multiples of the supply frequency, drawn by drives, rectifiers, UPS systems and LED drivers. They do no work, but they heat every conductor they pass through.
  2. An active harmonic filter measures the distortion and injects its mirror image, so the two cancel. It adjusts continuously, and it does not resonate the way a capacitor bank can.
  3. Installed at one point, usually the main board, it cleans the current between itself and the grid. The feeders and boards between the filter and the drives still carry the distortion, and its heat.
  4. HarmoniQ’s saving is three lines on one invoice: 10–20% fewer kWh, power-factor penalties eliminated and capacity charges reduced, proven at your own meter.

This explainer sets out what harmonic distortion costs, how an active harmonic filter works, where it stops, and how HarmoniQ treats the same problem across the network rather than at one point.

01Harmonics are made inside your own network

Variable-speed drives, rectifiers, UPS systems, LED drivers, welders and switched-mode power supplies are non-linear loads: they draw current in sharp pulses rather than a smooth sine wave. Those pulses are harmonics, currents at multiples of the supply frequency, and the equipment that draws them sends them back into the network every other machine shares.

The more drives and rectifiers a site runs, the more distorted its current becomes. The distortion is made on site, by the site’s own equipment, and it spreads from the machine that made it to the board, the feeder, the busbar and the transformer.

02Harmonics are heat you pay for

Harmonic currents do no useful work, but they flow through every conductor between the load and the supply, adding I²R losses on the way. Their losses rise faster than the current itself: eddy-current loss in a transformer winding grows with the square of the harmonic order, which is why IEEE C57.110 derates transformers that carry distorted current. Triplen harmonics, the 3rd, 9th and 15th, add in the neutral instead of cancelling, so a neutral can carry more current than the phases.

Heat ages insulation. By the Arrhenius rule, every 10 °C a winding runs above its rating halves its life, so the motors, transformers and cables that carry harmonic current wear out sooner. That is the cost a compliance report does not show.

Exhibit 1Where harmonic current costs a site · the mechanism, and where it shows
WhereWhat harmonics doWhat it costs
Cables and busbarsExtra current, at frequencies where skin effect raises resistanceI²R losses, paid for on the meter
TransformersEddy-current loss rising with the square of the harmonic orderDerating under IEEE C57.110: capacity paid for, not usable
Neutral conductorsTriplen harmonics add instead of cancellingOverheated neutrals
MotorsExtra heating in windings and rotorShorter insulation life, by the Arrhenius rule
Capacitor banksResonance with the network’s inductanceAmplified harmonics and failed capacitors
The connectionDistortion beyond the limits in the connection agreementA compliance problem with the utility

The pointIEEE 519 limits what a site puts onto the supply at its point of common coupling. It says nothing about the harmonic current flowing through the plant inside, where the losses and the heat are.

03How an active harmonic filter works

An active harmonic filter is power electronics connected in parallel with the load. It measures the current continuously, calculates its harmonic content, and injects the mirror image, so the two cancel and the current upstream of the filter returns towards a clean sine wave.

That makes it a real step up from passive filtering. A passive filter is a network of reactors and capacitors tuned to one or two harmonic orders, usually the 5th and 7th: it treats only what it was tuned for, and its tuning drifts as its components age. An active filter treats the spectrum it measures and adjusts as the load changes. It behaves as a controlled current source rather than a fixed capacitance, so it does not form the parallel resonance a capacitor bank does. Most models also correct displacement power factor, and some redistribute current across the three phases.

Exhibit 2Passive and active harmonic filters · how each works at the point where it is connected
Passive (tuned) filterActive harmonic filter
How it worksReactors and capacitors tuned to chosen harmonic ordersPower electronics inject the mirror image of the distortion
Harmonics treatedThe one or two orders it was tuned forThe spectrum it measures, within its rating
A changing loadFixed: its performance drifts as components ageAdjusts continuously
ResonanceCan resonate with the network if the load or supply changesDoes not form the parallel resonance a capacitor bank does
Power factorSupplies a fixed amount of reactive powerCorrects displacement power factor, in most models
Where it cleans the currentBetween itself and the gridBetween itself and the grid

04Where an active filter stops

An active filter cleans the current where it is connected. Installed centrally, at the main board, which is where most are fitted, it cleans the current the transformer and the meter see. The feeders and boards between the filter and the drives still carry the distortion, and its heat.

That is why an active filter can bring a site within IEEE 519 at its connection while the plant inside runs as hot as before. The kilowatt-hours fall only by the losses the filter removes upstream of where it is connected, so the energy saving stays modest. Fitting a filter at each large drive moves the cleaning closer to the source, but each filter is still a single-purpose box, and the reactive current of the fixed-speed motors and the imbalance between the phases remain separate problems.

The pointAn active filter is a compliance tool at the point where it connects. The cost of harmonics is paid across the whole network.

05Harmonics removed where they start

How HarmoniQ treats harmonics

HarmoniQ removes harmonic distortion, reactive power and phase imbalance close to where each arises, rather than at a single point, so less of the waste current travels through the cables, transformers and switchgear it would otherwise heat.

At the load

HarmoniQ Alpha

Fitted at each machine, it cleans the current where it is drawn, so every cable upstream carries less of it and runs cooler.

At the drives

HarmoniQ Delta

Fitted at the drives panel, it cleans the current where the drives distort it, before it spreads to the feeder, busbar and transformer.

At the incomer

HarmoniQ Sigma

At the main switchgear, it corrects reactive current where the network meets the grid, so the supply and the meter see cleaner current.

All three are shunt-connected, outside the supply path, and install with zero disruption to production. Together they correct power factor to 0.98 or better across the network, without adding the resonance risk a capacitor bank brings.

Each unit goes where the survey finds its problem. A machine on a variable-speed drive generally gets a Delta, at the drives panel, to take out the harmonics the drives make; a fixed-speed machine gets an Alpha, which corrects its power factor and trims its harmonics. The Sigma sits at the incomer, where it helps when the supply itself arrives distorted, by solar inverters on the network, for example.

The difference shows on the meter. An active filter leaves the kilowatt-hours largely where they were. HarmoniQ’s figure is 10–20% fewer kilowatt-hours for the same output, and the performance guarantee is written against those kilowatt-hours, proven by switching the system on and off at your own meter.

06What it’s worth: the invoice, and the plant

Three lines on the same invoice fall when the waste stops. The first is energy, and it is the line our minimum performance guarantee is written against: kilowatt-hours at the meter, not the bill, which also moves with tariffs and charges outside anyone’s control.

Fewer kilowatt-hours for the same output
10–20%
Power factor, so reactive charges fall away
0.98+
Off the total bill, where all three lines apply
Up to 25%
Exhibit 3An active filter at the main board and HarmoniQ · where each moves the bill and the plant
Active filter at the main boardHarmoniQ
Harmonics at the connectionWithin IEEE 519, where sized for itWithin IEEE 519 and IEC 61000 limits
Harmonics inside the networkStill flowing between the filter and the loadsRemoved close to where they start
Power factorCorrected at the filter, in most modelsCorrected to 0.98 or better across the network
Phase imbalanceIn some models, at the filterCorrected across the network
Energy (kWh)Falls only by the losses upstream of the filter10–20% fewer kWh for the same output
Equipment lifeA cooler transformer; the plant inside unchanged2–4× longer downstream equipment life

Every site’s loads, tariff and harmonic spectrum are different, and the figures above describe the mechanism, not a quote. Our engineers will measure your harmonic spectrum and model the distortion removed, losses reduced and capacity freed for your specific connection. Get in touch for a site assessment.

07Three steps. Zero disruption.

  1. Assess Our engineers measure your harmonic spectrum, current and voltage distortion, power factor and load profile, and model the distortion removed, losses reduced and capacity freed for your site.
  2. Install Each unit is sized to your site and installed in parallel, where its problem starts — no circuits broken, no production interruption.
  3. Verify Results are proven at your own meter — switchable on and off so you can confirm the difference in metered results in real time.

08What we hear, and the reality

“Our drives have built-in reactors, so harmonics are handled.”

Line reactors and DC chokes trim a single drive’s harmonics, but they leave plenty on the board, and they do nothing for the combined distortion of a whole plant. What remains still heats every conductor it passes through.

“Harmonics are a compliance box to tick, not a cost.”

IEEE 519 is the visible part, and it is measured at the connection. The cost is the heat inside: losses on the meter, derated transformers and shorter equipment life, every hour the distortion flows.

“An active filter at the main board does the same job.”

It meets the limit where it connects, and the meter sees cleaner current. The feeders and boards between the filter and the drives still carry the distortion, so the kilowatt-hours barely move. HarmoniQ removes it close to where it starts.

Sources

  • Standards. IEEE 519-2022 sets harmonic limits at the point of common coupling: 8% voltage distortion at 1 kV and below, 5% from 1 kV to 69 kV, and current limits that depend on the site’s short-circuit ratio. The IEC 61000 series sets equipment emission limits and measurement methods, and IEEE C57.110 sets how far a transformer must be derated for distorted current.
  • How the technologies work. The descriptions of passive and active filters are general engineering practice. Where a filter is connected, and what it is rated for, decide what any one installation achieves.
Next stepenquiries@harmoniqtechnologies.com

Clean the Current Where It Starts

Our engineers will measure your harmonic spectrum, model what removing it is worth, and prove the result at your own meter.