Insights / Power quality foundationsInteractive

The Seven Sins of Power Quality

Seven distinct physical phenomena corrupt the sine wave between the utility and the load. Each does its own kind of damage, carries its own cost and calls for its own remedy.

Written by
HarmoniQ Engineering Team
Published
May 2026
Reading time
13 minutes
Inside
1 exhibit · 1 interactive figure

In brief

  1. Seven distinct phenomena corrupt the sine wave: harmonics, reactive power, oscillations, unbalance, voltage variations, transients and flicker. Each has its own physics, cost and remedy, and most sites carry several at once.
  2. Harmonic and reactive current do no work but still heat every conductor they pass through. Heat ages insulation: a transformer designed for 25 years, run 20 °C hot, lasts about six.
  3. The rest cost reliability and equipment life: capacitor switching sets the network ringing, unbalance drives a backward field through motors, sags trip drives, and transients weaken insulation until it fails.
  4. HarmoniQ removes harmonics, reactive power and unbalance where they arise, and helps with transients and flicker; voltage variation needs other equipment. For the sins it addresses, the result is metered: 10–20% fewer kWh.

Every industrial site is promised a clean 50 or 60 hertz sine wave, held within tight tolerances, and every site receives something worse. The gap between what was contracted and what arrives, counted in kilowatt-hours of loss, degrees of extra heat and years of equipment life, is the native currency of power quality. Seven distinct failures of the waveform account for nearly all of it.

The seven sins · clean sine against the affected waveModelled · 50 Hz · per unit of nominal peak

Harmonics · Current THD

23%

√(0.20² + 0.12²): a 5th at 20% and a 7th at 12% of the fundamental. RMS current rises with √(1 + THD²), so I²R heat rises by 5%.

Sin I · Pride

Harmonics

Currents at whole multiples of the supply frequency, drawn by non-linear loads, that bend the sine out of shape.

Typical sources
Variable-speed drives, rectifiers, UPS, switched-mode power supplies and LED drivers.
What it costs
Extra I²R heat in every cable, busbar and winding, overloaded neutrals, and transformers that must be derated.

Where HarmoniQ stands

Where drives push harmonics high, a Delta goes at them and cancels the harmonic current at its source. The Alpha trims it at each machine, and the Sigma helps where the incoming feed is already distorted.

Each trace is drawn from a line or two of maths, given in the reading above it, not from a meter. Where an effect is too small to see at this scale it is exaggerated, and the reading says so.

The moral register is useful, and the sins are not metaphorical. Each is a physical phenomenon with its own signature on the waveform and its own way of turning a site's electricity into heat, vibration, torque ripple and early failure. Most sites carry several at once. Pick one above to see what it does to the wave.

For each we give the physics, what is happening to the waveform; the cost, what the site pays to host it; and the remedy, including, plainly, where HarmoniQ stands and where it does not. All of it can be measured with a power-quality analyser, and the outcome HarmoniQ guarantees, fewer kilowatt-hours for the same output, is proven at the site's own meter.

01Pride: harmonics

The one who believes the rules do not apply. Each harmonic asserts its own frequency and refuses to bow to the fundamental. The clean sine becomes a peaked, notched shape that was never promised and is never what the load requires.

The physics

The supply oscillates at 50 Hz across most of the world, and at 60 Hz in North America and parts of South America and Asia. Harmonics are whole multiples of that fundamental, 150, 250 and 350 Hz and upwards on a 50 Hz supply, which stack on the clean sinusoid and bend it out of shape.

They start at non-linear loads: variable-speed drives, switched-mode power supplies, LED drivers, rectifiers, UPS, arc furnaces and induction heating. These loads draw current not as a smooth sine but in sharp bursts near the peaks of the voltage. Fourier analysis resolves the bursts into the fundamental plus a series of harmonic currents, in which the 3rd, 5th, 7th, 11th, 13th, 17th, 19th, 23rd and 25th dominate.

The distortion is measured as total harmonic distortion, THD: the root-sum-square of the harmonic currents as a share of the fundamental. The figure's case, a 5th at 20% and a 7th at 12% of the fundamental, works out at 23%.

The cost

The damage is thermal. Harmonic current flows through every cable, busbar, transformer winding and motor stator between the point of common coupling and the load, and heats each one as I²R loss while doing no useful work. RMS current rises with √(1 + THD²), so 23% THD adds about 5% to the I²R loss on its own. In transformer windings it is worse: eddy-current loss rises with the square of the harmonic order as well as of the current, so a 5th harmonic at 20% of the fundamental makes as much eddy-current loss as the fundamental itself. That is why IEEE C57.110 sets out how far a transformer must be derated when it feeds harmonic loads.

Triplen harmonics, the 3rd, 9th and 15th, are the most troublesome. Under balanced loading the three phases' fundamental currents cancel in the neutral; the triplens add. On heavily non-linear single-phase loads the neutral can carry more current than any phase conductor, a duty that neutrals sized for linear loads were never meant to carry.

The pointHeat ages insulation. By the Arrhenius rule that IEEE and IEC thermal standards build on, every 10 °C of sustained extra temperature halves insulation life. A transformer designed for 25 years, run 20 °C hot by harmonic heating, lasts about six.

The remedy

Remove the harmonic current where it is made. Wherever drives push harmonics high, a HarmoniQ Delta goes at them and cancels their harmonic current there, self-tuning as the load changes, before it spreads to the cables, busbars and transformers upstream. Its settings decide how much of each harmonic it cancels and which it deals with first, so it can be set to the distortion a site actually has. The other units help as well: the HarmoniQ Alpha trims harmonics at the machines it serves, though without a Delta’s finish, and the HarmoniQ Sigma, at the top of the network, helps where the incoming feed is already distorted, as on sites with solar panels and their inverters. HarmoniQ is designed to help a site meet the harmonic limits of IEEE 519-2022, and less harmonic current means less heat in everything it would have passed through.

02Greed: reactive power

The one who takes more than it needs. It draws current that does no work. The utility delivers it, the cables carry it, the transformers warm with it and the site pays for it. Nothing useful is produced.

The physics

An AC system carries two kinds of power. Real power, in kilowatts, does work: it turns motors and heats elements. Reactive power, in kVAr, does not. It is energy shuttling between the supply and the magnetic fields of motors and transformers, or the electric fields of capacitors and cables, stored in one quarter-cycle and returned in the next. The net work is zero, but the current that carries it must still flow, and every conductor it flows through turns some of it into heat.

Power factor is the ratio of real power to apparent power. With a sinusoidal current it equals cos φ, where φ is the angle by which the current lags the voltage. A purely resistive load runs at 1.0; an uncorrected site full of induction motors often runs between 0.75 and 0.85. The lower it runs, the more current it draws for the same work: at 0.80, 1 ÷ 0.80 = 1.25 times as much, with 1.25² = 1.56 times the I²R heat.

The cost

Utilities bill for it in three overlapping ways: kVA demand charges, which meter apparent power, real and reactive alike; reactive-energy charges per kVArh; and penalty clauses when power factor falls below a contractual threshold, commonly 0.9 or 0.95. Inside the site, reactive current also uses up the thermal headroom of every asset between the load and the transformer.

Worked exampleA 1,000 kVA transformer at 0.85 can deliver 850 kW of real power; at 0.98 the same transformer delivers 980 kW, 15% more from the same copper and iron.

The remedy

Correct it where it is drawn, and again where the site meets the grid. Every HarmoniQ unit, Alpha, Delta and Sigma, improves power factor where it sits, and a site assessment decides where each one goes. Together they correct the site's power factor to 0.98+. Power-factor penalties fall away wherever the utility levies them, and capacity charges fall as correction frees apparent power the site no longer needs to contract for.

03Lust: oscillations

The one that cannot settle. Energy sloshes between inductance and capacitance, unable to find equilibrium, and the waveform rings at frequencies it was never meant to carry.

The physics

Any circuit with inductance and capacitance is a resonant LC system. Energy stored in an inductor's magnetic field passes to a capacitor's electric field and back, at a frequency set by the two: f = 1 / (2π√LC). Only resistance dissipates it, so in a lightly damped network a ring can last tens of milliseconds or more.

The commonest trigger is switching a capacitor bank. With the supply transformer, the bank resonates at a harmonic order of √(Ssc ÷ Qc), the transformer's short-circuit power over the bank's rating.

Worked exampleA 300 kVAr bank on a 1,000 kVA transformer at 6% impedance resonates near 373 Hz, between the 7th and 8th harmonics of a 50 Hz supply, so it will amplify any 7th-harmonic current the drives inject. Switch the bank in at the voltage peak and the bus voltage collapses towards zero, then overshoots, to 1.7 times nominal in the figure's case, before ringing away within a cycle.

Long cables between drives and motors add resonances in the kilohertz range. Unlike harmonics, these oscillations are not locked to whole multiples of the supply frequency: they ring at whatever frequency the network sets.

The cost

The damage is more diffuse than harmonic heating, and more systemic. Drives, PLCs and protection relays all expect a clean fundamental, and a ringing supply brings nuisance faults, phantom trips and shutdowns nobody can explain. Capacitors are stressed by the overvoltage and the resonant current. On a motor supply, oscillatory current becomes torque ripple at the shaft, and so vibration and bearing wear. Inverter-based equipment, from UPS to solar PV and battery storage, is particularly exposed, because its controller can read the disturbance as a grid fault.

The pointThe commercial cost is reliability. A site that trips once a month on an unexplained power-quality event pays for that downtime whether or not it ever finds the oscillation behind it.

The remedy

Remove the triggers. HarmoniQ's part is to take away two of the commonest causes, not to damp the ring itself. It removes harmonic current where it is made, so a resonance near a harmonic has less to amplify, and it corrects power factor to 0.98+ through the network, cutting a site's reliance on switched capacitor banks, the usual source of the ring. Where a capacitor bank stays, the standard fix is to detune it with series reactors, which moves its resonance away from the harmonics the site produces.

04Envy: network unbalance

The one who cannot bear inequality. Three phases that will not tolerate their differences, and currents that flow not because any load needs them but because the asymmetry forces them to.

The physics

A three-phase supply is, by contract, symmetrical: three voltages of equal size, 120 electrical degrees apart. In practice the phases are rarely equal. Single-phase loads spread unevenly across a distribution board pull them apart, and some unbalance arrives already present in the supply.

IEC 61000-4-30 measures it through symmetrical components, as the negative-sequence voltage over the positive-sequence voltage, and EN 50160 expects it to stay within 2% for normal supply. A couple of per cent barely shows on a phase-by-phase voltmeter, yet the negative-sequence component is a real and destructive presence: in a motor, it drives a magnetic field that rotates backwards.

The cost

Motors pay first, and disproportionately. The backward field induces rotor current at nearly twice the supply frequency, heat that makes no torque. NEMA MG-1, which measures unbalance as the largest deviation from the average phase voltage, puts the current unbalance in a running motor at six to ten times the voltage unbalance. It recommends derating a motor once unbalance passes 1%, and running none above 5%.

Current unbalance in a running motor, per unit of voltage unbalance
6–10×
Voltage unbalance above which NEMA MG-1 recommends derating a motor
1%
Voltage unbalance above which it recommends running no motor at all
5%

Unbalance also drives circulating and neutral current through windings, transformer coils and busbars, and torque pulsation at every induction motor on the bus, which becomes vibration, bearing wear and shaft fatigue. Few sites know their own figure, because unbalance is rarely metered continuously.

The remedy

Balance the currents. HarmoniQ balances the phase currents across the network, which cuts the circulating and neutral current that uneven loading forces through the site.

05Gluttony: voltage variations

The one that cannot stop feeding, or cannot feed at all. A supply that sags under load and swells when the load is light, so every component on site sees a voltage it was not designed for.

The physics

Voltage variation is the RMS voltage moving away from nominal, from a sag or swell lasting a few cycles to under- or over-voltage that persists for hours. Sags come from heavy aggregate load, large motor starts, faults elsewhere on the network and weak supplies. Swells come from light load on a strong supply, faults on another phase, or a capacitor bank over-correcting and lifting the local voltage.

EN 50160 expects the utility to hold the voltage within ±10% of nominal for 95% of each week, and counts a dip whenever it falls below 90%. Even inside that band the supply can wander, and every load on site moves with it.

The cost

Every piece of electrical equipment is designed for a nominal band, and outside it, behaviour degrades in predictable ways. A motor's torque falls with the square of the voltage, so 10% under-voltage costs 19% of its torque, and a loaded motor draws more current to compensate, so its windings run hotter. Drives trip on under-voltage. Over-voltage pushes transformer and motor cores towards saturation, which raises core loss and iron temperature, and it stresses electronics.

The thermal cost compounds. Under-voltage drives current up, current drives I²R heat up, and heat drives insulation ageing. The damage is real whether the supply dips for a tenth of a second or sits low all afternoon.

The remedy

This one is not HarmoniQ's to fix, and it is better said plainly. HarmoniQ does not regulate voltage. Its units are shunt-connected and never sit in the supply path. Sags, swells and sustained under- or over-voltage need other equipment:

  • A UPS or ride-through for sensitive loads.
  • Voltage regulation where the supply wanders.
  • Soft starters or drives to tame large motor starts.
  • A conversation with the utility about the supply itself.

06Wrath: transients

The one that strikes without warning. Brief, violent and gone before most recording meters can trigger.

The physics

A transient is a brief, high-magnitude voltage or current event lasting from under a microsecond to a few milliseconds. IEEE 1159 sorts them into impulsive transients, a single sharp spike like the one in the figure, and oscillatory ones, a ring like the capacitor switching above. The sources are many but finite: lightning on the supplying network, capacitor-bank and load switching, fault clearing upstream, inductive loads switching off inside the site, and neighbours on the same medium-voltage feeder.

The magnitudes are large. A 6 kV surge on a 400 V network is more than ten times the 566 V peak of the line-to-line voltage, and it finds the weakest point in the insulation, often a section already weakened by years of heat.

The cost

Transient damage is cumulative, then sudden. Insulation degrades a little with each event until a final one causes a flashover: a transformer failure, a winding short-circuit, a drive's electronics destroyed. The failure looks sudden but ends a long history nobody recorded. Transients are the hardest of the seven to see, over before most instruments trigger and with frequency content beyond their bandwidth. They show themselves in the post-mortem: the carbonised winding, the punctured capacitor, the blown semiconductor.

The remedy

Two layers.

Layer one

Surge protection

Lightning-class surges need a rated surge protective device at the incomer, and nothing here replaces one.

Layer two

HarmoniQ

HarmoniQ helps with the transients that reach equipment, and it takes away the steady heat that leaves insulation weak when a transient arrives: insulation that runs cooler keeps more of its strength.

07Sloth: flicker

The one that cannot hold steady. A supply that wobbles, and lamps that flicker not because they are failing but because the voltage is.

The physics

Flicker is a slow modulation of the RMS voltage, at between about 0.5 and 25 swings a second: slow enough for the eye to see in lighting, and measurable as a distinct signal. The classic sources are loads that pulse: arc furnaces, spot welders and large reciprocating compressors. Each draws a current that swings well below the supply frequency, and the supply's impedance turns that current swing into a voltage swing on the bus.

The measure is short-term flicker severity, Pst, defined by IEC 61000-4-15 over ten minutes, with a two-hour counterpart, Plt. Pst = 1 is the conventional threshold of irritation, and the eye is most sensitive to swings near 8.8 a second, the rate the figure uses. EN 50160 expects Plt to stay at or below 1 for 95% of each week.

The cost

Flicker does damage on two fronts. Where people work, it brings eye strain and headaches. In production, it disturbs sensitive electronics, false-triggers photo-sensors and tells every instrument on the bus that the supply is under stress. The slower cost is mechanical: the same modulation means pulsating torque in induction motors, pulsating heat in elements and pulsating magnetisation in transformer cores, stress at a frequency no design-life calculation contemplated.

The remedy

HarmoniQ helps with flicker, but how far it falls on a given site depends on the source, so it is measured, not promised. The heaviest source, the arc furnace, sits on medium-voltage supplies, beyond HarmoniQ's 600 V range.

08The redemption is measurable

The seven share a root: the waveform that reaches an industrial site is not the waveform its supply contract describes, and most sites carry several of the seven at once.

Where HarmoniQ stands

HarmoniQ's three units each work where they sit.

At the load

HarmoniQ Alpha

Fitted at each machine, it cleans the current where it is drawn, so every cable upstream carries less of it and runs cooler.

At the drives

HarmoniQ Delta

Fitted at the drives panel, it cleans the current where the drives distort it, before it spreads to the feeder, busbar and transformer.

At the incomer

HarmoniQ Sigma

At the main switchgear, it corrects reactive current where the network meets the grid, so the supply and the meter see cleaner current.

Between them they remove harmonics, reactive power and unbalance where they arise, help with transients and flicker, and take away the triggers of oscillation. Voltage variation needs other equipment.

Exhibit 1The seven sins, and where HarmoniQ stands
SinPhenomenonWhat it costsWhere HarmoniQ stands
I · PrideHarmonicsHeat in cables and windings, overloaded neutrals, derated transformersHarmoniQ Delta, with help from the other units
II · GreedReactive powerExtra current, power-factor penalties, kVA and capacity chargesEvery unit improves it; together, to 0.98+
III · LustOscillationsNuisance trips, stressed capacitors, vibrationIndirectly, by removing the triggers
IV · EnvyNetwork unbalanceMotor heating, circulating and neutral current, torque pulsationHarmoniQ balances the phases
V · GluttonyVoltage variationsDrive trips, hot motors, saturated coresNot HarmoniQ: a UPS or voltage regulation
VI · WrathTransientsCumulative insulation damage, then sudden failureHelps; surge protection still needed
VII · SlothFlickerEye strain, disturbed controls, pulsating torqueHelps, site by site

For the sins it addresses, the redemption is not moral. It is metered:

Fewer kWh for the same output, at the meter the guarantee is written against
10–20%
Power factor, so reactive-power penalties fall away wherever they are levied
0.98+
Longer downstream equipment life, by the Arrhenius rule
2–4×
Disruption to install: shunt-connected, never in the supply path
0

On the invoice, the kilowatt-hour saving is one of three lines. Energy falls 10–20%; power-factor penalties are eliminated, with power factor corrected to 0.98+; and capacity charges fall as correction frees apparent power. Where all three apply, that is up to 25% off the total electricity bill.

The distortions stay in the physics. What changes is how far they travel: removed where they arise, they no longer cross the site as heat. The facility keeps what it was always paying for.

Next stepenquiries@harmoniqtechnologies.com

Find Out Which Sins Your Site Carries

We quantify the opportunity on your site with zero disruption. We offer minimum performance guarantees.